Previous Page  27 / 116 Next Page
Information
Show Menu
Previous Page 27 / 116 Next Page
Page Background

www. e l e c t r i c a l c o nn e c t i o n . c om . a u

2 7

with

Chris Halliday

of circuits. Rating factors are shown in Tables

27 to 29 for such factors as cables in heated

concrete, soil temperature, burial depth and

soil thermal resistivity.

In using Tables 4 to 21, circuit designers or

electricians should consider the following

cable situations:

>

Vertically or horizontally spaced;

>

touching the surface of, say, wall lining

material;

>

exposure to the sun;

>

enclosed or not;

>

partly or completely surrounded by

thermal insulation; and,

>

buried directly or in an enclosure such as

conduit.

They should then go to the correct

column of the table.

VOLTAGE DROP

Too long a cable run with too much load

will cause excessive voltage drop, which

may result in unsafe or non-operation of the

equipment on that circuit.

This will breach the Wiring Rules, so we

must consider voltage drop when selecting

a cable (see

Electrical Connection

Autumn

2015, page 44).

FAULT LOOP IMPEDANCE

The loop impedance of circuits must

be considered for all circuits and should

comply with Tables 8.1 and/or 8.2 of

the Wiring Rules.

Table B1 provides guidance on circuit

lengths. Voltage drop requirements

will generally, but not always, be

more stringent than loop impedance

requirements. Further detail is provided in

the aforementioned article.

SHORT-CIRCUIT TEMPERATURE

Cables may have to endure the thermal

effect and mechanical forces caused by fault

currents for up to five seconds.

Therefore we must check the minimum

cable size that can withstand these effects

by applying the following formula:

S

=

√ I

2

t

K

2

where

S = size of the current-carrying

component (mm²).

I = short-circuit current (amps).

t = duration of the short circuit current

(seconds) – check protective device

information for the fault level.

K = temperature constant depending on

the material of the current-carrying

component.

Some examples are provided in

AS/NZS 3008.1.1 for reference.

REPUTABLE SUPPLY

If the Infinity and Olsent debacle has

taught us anything, it is that we should buy

only reputable brand cables from reputable

suppliers.

This goes for all other electrical

equipment and components. The message

from government fair trade departments

is: “If it sounds too good to be true – then it

probably is”.

CONCLUSION

Selecting a particular type and size of

cable is not easy, and there will be other

factors not included here.

Failure to consider all requirements may

mean that people are put at risk, or the

electrician must bear the cost of returning to

remedy the installation.

> Power Logic

www.powerlogic.com.au

EMONA

email

testinst@emona.com.au

web

www.protag.com.au

ProTag PrimeTest Elite

Australia’s Most Advanced Test & Tag System

Sydney

Tel

02 9519 3933

Fax

02 9550 1378

Melbourne

Tel

03 9889 0427

Fax

03 9889 0715

Brisbane

Tel

07 3275 2183

Fax

07 3275 2196

Adelaide

Tel

08 8363 5733

Fax

08 83635799

Perth

Tel

08 9361 4200

Fax

08 9361 4300

High Definition

Colour Display

In-Built Camera

with Flash

USB for Data

Up/Down Load

Bluetooth For

Printer & Scanner

The new ProTag Elite System tests portable appliances & RCDs, takes asset photos,

prints Elite UV resistant test tags & downloads results to PC. Mains & battery powered.

Faster testing & asset management for mining, construction, factories & workshops.