Previous Page  45 / 108 Next Page
Information
Show Menu
Previous Page 45 / 108 Next Page
Page Background

www. e l e c t r i c a l c o n n e c t i o n . c om . a u

45

BY

DAVID

HERRES

them is probably faulting. Electrical

equipment, especially motors, tend

to draw more current as they age,

due to internal insulation gradually

breaking down. This can also happen if a

transformer is connected.

A hair dryer or laptop computer,

when the internal battery is being

charged, may be the culprit. Unplugging

connected loads one at a time, with

a clamp-on ammeter at the entrance

panel, will quickly locate the fault. The

Amprobe ‘hold’ function is useful in this

procedure.

Nuisance tripping can also be a

problem with residual current devices

(RCDs). In the United States and Canada

these are known as ground-fault circuit

interrupters (GFCIs). The purpose and

inner workings of both are similar, but

the circuit deployment varies due to

different phasing arrangements.

NEC and CEC, as well as the Australian

and New Zealand Wiring Rules, require

such devices in sensitive locations –

wherever the proximity of electrical

power and water may lead to a shock.

Since their introduction in the 1960s,

and subsequent widespread use, RCDs

have greatly reduced the number of

non-utility electrocutions, especially

in homes.

The equipment-grounding conductor

usually completes the circuit to the

entrance panel, then the over-current

device trips. However, in some instances

that conductor breaks or has not been

properly hooked up. The result can be an

electric shock – sometimes fatal.

The RCD takes the form of a breaker

in the entrance panel or load centre,

a receptacle at the wall outlet, or a

moulded-case device built into a power

cord and located adjacent to the plug.

The hot wire and neutral return

conductor of a 240V circuit both

pass through the device. Normally,

the current in the supply and return

conductors is equal (conforming to

Kirchhoff’s Current Law that electrical

current is everywhere the same in a

non-branching circuit).

In a two-fault situation (involving

connectivity of the hot wire and loss

of connectivity of the equipment-

grounding conductor), when someone

touches the energised metal, some of

the current goes to earth.

The RCD monitors both current paths,

performing a continuous differential

measurement. If the difference exceeds

a specified limit, typically 6mA, the

device interrupts the circuit. The amount

and duration of the brief electric shock

is not enough to constitute a hazard.

Many of these devices combine the

function of an over-current device, and

they can also be used as a switch by

pressing the ‘test’ button.

The newer RCDs have an LED that

indicates a tripped condition, so it is

possible to know at a glance where

the problem lies. Moreover, if the RCD

is not getting power, it will not reset,

providing immediate information on the

status of the upstream portion of the

branch circuit.

Unfortunately, RCDs are prone to

nuisance tripping, which is often

caused by a defective load. The first

step is to unplug all downstream loads,

one at a time.

(Remember: nothing that happens

upstream of the RCD, including

conductor imbalance, can cause tripping.

The device monitors only downstream

wiring, devices and loads.)

Some loads are incompatible with

RCDs, and refrigeration equipment is

one example.

In a hermetically sealed compressor,

motor windings are submerged in

the grounded refrigerant, and any

imperfection in the light coating of

insulation will allow current leakage to

ground.

Moreover, an undetected nuisance-

tripping incident can lead to the loss of

freezer contents.

A dedicated non-RCD circuit should be

run for a refrigerator, even in a kitchen.

RCDs should not be used in circuits

for fire alarms, life support and other

essential services.

If the cause of nuisance tripping is not

apparent, and substitution has ruled

out the device, take a good look at the

wiring. Cable rubbing on grounded

metal pipe or an errant nail can create

a problem, or there may be moisture in

the wall.

Does the nuisance tripping occur

after heavy rain? Perhaps an outdoor

receptacle has been bugged off a

kitchen or bathroom receptacle to

obtain the required RCD protection.

If cable connectors have been over-

tightened in older concrete block or

masonry constructions with metal

wall boxes, there may be enough

current leakage to cause RCD tripping.

If so, it may be possible to loosen the

connectors and slide in a slit piece of

cable jacket.

If wiring runs are suspected, the

diagnostic procedure is to progressively

isolate segments of the branch circuit

by temporarily unhooking the hot

wires, one at a time, until the fault has

been located.

However, in residential construction

most of the wiring is behind finished

walls, so some hard work may be

in order.

Since their introduction in the 1960s, RCDs

have greatly reduced the number of non-utility

electrocutions, especially in homes.