Previous Page  46 / 116 Next Page
Information
Show Menu
Previous Page 46 / 116 Next Page
Page Background

4 6

E L E CT R I C AL CONNE CT I ON

AUTUMN 2 01 5

A 3% voltage drop = 0.03 x 230 = 6.9V

(this value must not be exceeded).

The current for the calculations will be

8A, as the socket outlets will be distributed

along the circuit (refer Clause 3.6.2

exception 1 of the Wiring Rules).

The impedance method:

The resistance of the cable is found by

using Table 35 of AS/NZS3008.1.1 and the

75°C value, i.e.: 9.01Ω/km.

Vd = I Zc

= 8 x 9.01/1000 x 40 x 2 (don’t forget

there are two conductors, the active and

the neutral return).

= 5.8V. This value passes the 3%/6.9V

voltage drop requirement set by the

installation requirements.

The mV/Ammethod

The Vc value is found for the 2.5mm²

cable using Table 42 of AS/NZS3008.1.1 and

the 75°C value, i.e.: 15.6mV/Am

Vd = (L x I x Vc)/1000

= (40 x 8 x 15.6 x 1.155)/1000 (don’t

forget the 1.155, as the mV/Am value in the

table is for a three-phase circuit)

= 5.8V

Both methods align – we must know

what we are doing! Again this passes the

3% requirement.

The simplified mV/Ammethod

Am/%V = (L x I)/%Vd

= (40 x 8)/3

= 106.7 Am/%V

Looking up Table C7 and selecting

the cable with a value not less than

106.7 Am/%V, we find that 2.5mm² is the

minimum size standard cable we can use

for this project. So, we come up with the

same result – it’s 2.5mm² cable.

OTHER CONSIDERATIONS

The Wiring Rules provides Table B1

for maximum route lengths for circuits

based on loop impedance.

This does not consider voltage drop,

so I have created Table 1 to compare

maximum route lengths for loop

impedance with voltage drop in the

same circuits.

I have also created Table 2, which

converts the values of loop impedance to

voltage drop.

A comparison of both tables shows that,

in most cases, voltage drop requirements

are often more stringent than loop

impedance requirements. Using loop

impedance route lengths or impedance

values in isolation is likely to result in

non-compliance with the Wiring Rules for

voltage drop.

CONCLUSION

Voltage drop must be considered when

designing and installing electrical wiring.

Compliance with voltage drop

requirements will be achieved mainly by

installing a large enough cable.

Total voltage drop in a low-voltage

installation is usually 5%. However, this

can be 7% if the supply comes from

the low-voltage terminals of a substation

on the premises and is dedicated to

the installation.

The allowable voltage drop must be split

between the consumer mains, sub-mains

and final sub-circuits to achieve an overall

compliant outcome.

Maximum route lengths and fault

loop impedance requirements do not

generally ensure compliance with voltage

drop rules.

> PowerLogic

www.powerlogic.com.au

Table 2 - Maximum Values of Circuit Resistance from Table 8.2 of the Wiring Rules

Converted to Voltage Drop

Active &

Neutral

(mm²)

Earth

(mm²)

No of

Phases

Protective

device rating

(A)

VOLTAGE DROP

Type B Type C Type D Fuses

1

1

1

6

16.0% 8.6% 5.1% 19.2%

1

1

1

10

16.0% 8.5% 5.1% 17.8%

1.5

1.5

1

10

16.0% 8.5% 5.1% 17.8%

1.5

1.5

1

16

16.0% 8.5% 5.1% 13.6%

2.5

2.5

1

16

16.0% 8.5% 5.1% 13.6%

2.5

2.5

1

20

16.0% 8.5% 5.0% 11.7%

4

2.5

1

25

12.4% 6.5% 3.9% 8.7%

4

2.5

1

32

12.2% 6.7% 3.9% 8.9%

6

2.5

1

40

9.4% 4.9% 3.1% 6.3%

10

4

1

50

9.1% 4.8% 3.0% 5.7%

16

6

1

63

8.8% 4.9% 2.7% 5.5%

Notes: 1. Halve the percentage voltage drop where the load is distributed over whole length of the circuit such as a

lighting or socket outlet circuit.

2. For three phase circuits multiply the percentage voltage drop values above by 0.866."

Designers and installers must

consider voltage drop to ensure

safety and proper operation

of the equipment.