Previous Page  44 / 116 Next Page
Information
Show Menu
Previous Page 44 / 116 Next Page
Page Background

4 4

E L E CT R I C AL CONNE CT I ON

AUTUMN 2 01 5

METHOD IN THE MADNESS

An acceptable drop

T

he voltage in a circuit will

drop due to the resistance and

reactance of cables.

Designers and installers must consider

voltage drop to ensure safety and proper

operation of the equipment, i.e.: adequate

voltage must be supplied.

If there is too much voltage drop the

equipment won’t work, or safety will

be compromised – such as a motor

overheating and catching fire.

We therefore need to consider voltage

drop before running cables and connecting

loads. A larger cable than intended may

be needed to ensure compliance with

voltage drop requirements. Considering the

voltage drop issue at the design stage of an

installation will help avoid problems.

The Wiring Rules – AS/NZS 3000, Section

2 at Clause 3.6 – provides the relevant

detail for low-voltage installations. Clause

7.3 covers stand-alone systems and Clause

7.5.7 covers extra-low-voltage installations.

All sparkies should be familiar with these

requirements.

LOW VOLTAGE

Clause 3.6.1 discusses having the

voltage for a piece of equipment higher

than the lower limit of the Standard for

that equipment.

The clause does allow for equipment not

covered by a Standard to function safely

at lower voltage, but it does not say this

negates other sub-clauses in Section 3.6.

Conductors shall be sized to ensure that

the voltage at any point in an installation

does not drop more than 5% from the

nominal (refer Clause 3.6.2). This equates

to 11.5V for a 230V system and 20V for a

400V system.

The clause does not consider transient

currents such as motor starting, solenoid

closing and other similar applications.

The permissible voltage drop can be 7%

if the supply comes from the low-voltage

terminals of a substation on the premises

and is dedicated to the installation (refer

exceptions for Clause 3.6.2).

The voltage drop limits just mentioned

are the total voltage drops for an installation.

Voltage drops in the consumer mains, sub-

mains and final sub-circuits must be tallied

to ensure compliance with the limits.

Most of the voltage drop could be

allocated to the final sub-circuit if there are

no sub-mains and very short consumer

mains. Likewise, long consumer mains and

sub-mains will severely limit the available

voltage drop in the final sub-circuit.

The old Australian Standards handbook

HB301, for designing to the Wiring

Rules, states that 2% to 3% is considered

reasonable for the final sub-circuits, but it

also discusses rearranging percentages for

a satisfactory outcome.

Prudent placement of main switchboards

and sub-boards will help to ensure that

voltage drop is not an issue. This is a design

matter and cannot be left to chance.

STAND-ALONE SYSTEMS

Stand-alone systems, in accordance with

Clause 7.3, are required to have a voltage

drop of no less than 11% from the nominal.

This must take account of the output

voltage of the source and the drop within

the installation under normal operating

conditions (refer exceptions for Clause 3.6.2).

It is really the same voltage-drop limit

as for a grid-connected system, as the

network company can have a drop of 6%

and the installation a further 5%.

EXTRA-LOW VOLTAGE

A maximum voltage drop of 10% for

extra-low-voltage installations, when

conductors are carrying the circuit-

operating current, is applied by Clause 7.5.7.

That is, unless the extra-low-voltage

equipment (not exceeding 50V AC or 120V

ripple-free DC) is specially designed to

operate over a wider voltage range.

The 10% limit excludes transient currents

caused by such things as motor starting,

solenoid closing and other similar events.

CALCULATING VOLTAGE DROP

Two methods are generally used for

calculating voltage drop, as provided by

AS/NZS 3008.1.1, and both use a value of

current in the calculation.

Clause 3.6.2 of AS/NZS 3000 provides

guidance on what value of current

should be used in calculations and

should not exceed:

>

total circuit current;

>

circuit maximum demand; or

>

circuit protective device rating.

For circuits such as lighting and socket

outlets, where the load is distributed over

the circuit length, half the current rating

of the protective device may be used for

calculations (refer exceptions for Clause 3.6.2).

The first method uses conductor

impedance, length and current for the

calculation. This is slightly complex, as the

resistance and reactance of the cable must

be known to allow calculation of the cable

impedance (refer Clause 4.3 of AS/NZS

3008.1.1).

The resistance and reactance values for

various cable types are provided by Tables

30-39 of AS/NZ 3008.1.1. For smaller cables

It might have been some

time since you learned about

voltage drop, so what are

the requirements and the

calculations?

Chris Halliday

explains.