Previous Page  69 / 116 Next Page
Information
Show Menu
Previous Page 69 / 116 Next Page
Page Background

www. e l e c t r i c a l c o n n e c t i o n . c om . a u

69

already widely available in a lot of

appliances but can also be used for

generation systems. For instance, a

utility could send out a signal either

because of power quality, cost or

an agreement with the customer to

reduce their generation by a nominated

percentage or disconnect from the grid

for a period of time.

The signals may be communicated via

an old fashioned ripple control

but, according to Glen, are more likely

to be sent via a dedicated link such as

3G to the installation or some form of

aggregation by the utilities over pole top

communication systems. They will be

used when there’s excess generation on

the network but also to export energy

from customers back onto the grid.

“At the moment we’re all about

stopping excess generation but there

may be times when grid support

modes are needed. At these times

utilities can request energy from

customers who have the facility and

have agreed to allow their energy to

be exported on demand – this will tie

in with some sort of financial benefit

to the customer.”

Voltage rise and voltage drop

calculations for grid connected

systems as part of the application

process have also been addressed in

the updated standard. NSW utilities

adopted the AS/NZS 4777.1 draft

recommendations in back in August

2013 and the utilities in other states and

territories will no doubt adopt them as

soon as it’s published.

“You’ll have to keep voltage rise

below 1% per network segment – so

1% from the inverter output to the

switchboard and then 1% from the

switchboard to the point of common

coupling which is usually the service

mains arm of the building. This is

hard to do on rural properties that often

have 16mm mains coming in

and long AC supplies from the

switchboard to where the house is and

where the solar is likely to be installed –

in this kind of scenario it’ll be well over

1% over 20m-30m. That calculation not

only needs to be done but needs to be

complied with as a 2% overall rule will

come into force with the publication of

AS/NZS 4777.1.”

GAIL

BRIGSY

DELIVERED DIRECT

TO YOUR DOOR

PHONE 1800 623 214 or visit

WWW.TRADESTUFF.COM.AU

Electrical Estimator’s Labour Unit Manual

14th Edition

CODE 583 . . . . . . . . . . . . . . . . . . . . . . . $120.00 (inc. postage)

This updated labour unit manual has been produced to assist contractors

to allow a realistic labour allocation to their jobs. These units have

been developed over a number of years using actual time studies. This

publication also includes a USB estimating spreadsheet and templates for

calculating hourly charge out rates and minor installation quotations.