Take advantage of communication opportunities provided by HART signals
Statistics from the HART Communication Foundation (HCF) show that around 64.9 million devices were installed throughout the world in 2008. Some 58% of these devices are equipped with communication capabilities such as HART or a fieldbus interface. The great majority (some 30 million devices) are HART capable. Although users want to know more about devices in terms of a secure, efficient and sustainable process, HART capabilities are used for only about 10% (approx. 3 million) of the devices.
The majority of users thus not only forgo the option of simplifying commissioning and maintenance but also miss out on the ability to gather important diagnostics data. One reason for this is that many planners were initially only interested in the device’s 4-20mA signal. Its HART capabilities, while not being considered a bother, were not included in any list of requirements. HART-capable I/O cards were rarely installed.
ADVERTISEMENT
However, the communication capabilities of devices are playing an ever-greater role. While increasingly networked production environments provide many advantages, they also require a consistent information flow. In other words, what is the use of a smart device if the relevant data is not available? In this context, HART communication represents an interesting option.
Bi-directional communication between PC and up to 32 field devices
When it comes to configuring and maintaining individual devices, users can perform the necessary tasks with a HART modem or a HART handheld. The disadvantage of this approach is that users are only able to access HART-capable devices and, when using a handheld, only temporarily. While these restrictions are tolerable for configuration, the procedure is not viable for the ongoing maintenance and monitoring of multiple important field devices. If the HART signal is to be put to more comprehensive use at a later time, normal I/O cards need to be replaced with HART-capable cards to enable communication with the higher-level asset management system. Replacing a number of cards is, however, highly expensive and has repercussions on the existing equipment and its function.
An alternative solution is HART multiplexing. A HART multiplexer organises bi-directional data exchange between a maximum of 32 field devices and a separate PC or controller. Users need to wire the 4-20mA signal to the controller and also implement a link to a transfer board. This does not impact the 4-20mA signal in any way due to capacitative decoupling of the information. The HART multiplexer takes up the decoupled HART signal and relays it via an RS485 interface. This enables consecutive communication with the devices via the HART multiplexer. If the connection volume is not sufficient, the transfer board can be extended by a second board.
Simple integration into the Ethernet infrastructure
The available concepts for communication between the multiplexer and PC depend on the application scenario.
• Implementation using an RS485-to-RS232 interface converter
• Data exchange with the Comserver via Ethernet TCP/IP.
The Ethernet-based option is best explained using an example: The temperature is measured using a temperature head transducer. Communication was previously restricted to 4-20mA signals; HART signals were not used. To improve plant monitoring and simplify the configuration of temperature ranges, the operator now wants to be able to communicate with the field devices. A number of the head transducers installed are HART capable. The sensors are located in an explosion hazard zone. For this reason, the operator installed an intrinsically safe head transducer and an additional Ex-i repeater power supply to separate the intrinsically safe and non-intrinsically safe circuit. This is not a safety function in the sense of functional safety in accordance with IEC 61508. Nevertheless, the operator wishes to improve the availability of the unit and its monitoring by using the HART information. Moreover, the data is to be transferred in a web-based manner via TCP/IP. The effort involved is to be kept to a minimum.
To this end, the operator requires HART-capable devices and HART-transparent Ex-i isolation amplifiers that do not degrade the signal through filtering. Clips for transmitting the 4-20mA signal to the control and the transfer board may be required as well, in addition to the transfer board for uncoupling the signals, the HART multiplexer, as well as a Comserver for communication via Ethernet TCP/IP. A PC with a suitable program is also required. The control cabinet can accommodate a HART multiplexer with two transfer boards and a Comserver. The additional devices, with a total width of 22 centimetres, enable the connection of 32 signals. Die HART-transparent isolation amplifiers do not need to be installed next to each other. The signals can instead be collected on the HART transfer board in the control cabinet and transferred to the multiplexer via ribbon cables. If the information is then to be communicated via Ethernet, the Comserver converts the signal from RS485 to TCP/IP and relays the data to the PC via the existing network structure.
Comprehensive monitoring and flexible parameterising of the field devices
After the HART multiplexer has been connected to the PC via Ethernet by means of the Comserver, the operator can call up the Comserver web interface for system configuration. To do so, the operator enters the IP address printed on the side of the device into the browser’s address list. The Comserver enables communication with multiple multiplexers. The operator will also require a HART OPC server, which can be ordered on the HART Communication Foundation homepage. Version 3.2 of the HART OPC server contains the Phoenix Contact HART multiplexer by default. Once all connected multiplexers and the field devices attached to them have been read-in, they are displayed in the software. Operators can now select devices and choose the “Properties” menu option to view all constituent data, such as the present process value, the date as well as the upper and lower measuring range limits or to enter a description. Further information on the status of the field device can be displayed if required. The HART OPC server supports all basic and general HART commands. In addition, the manual entry of device-specific HART instructions for parameterising is also possible if the manufacturer supports this function. The operator can finally save the HART information using a suitable commercial software.
The HART multiplexer enables improved use of the HART signals for optimizing both new and existing systems. By exchanging data with the HART devices in the field based on a multiplexer, operators gain more complete information on the process and are able to visualize the data, for instance via TCP/IP, at any desired location. The Phoenix Contact product portfolio offers all components required for this solution.
-