The Electrical Safety Office was notified of two separate incidents where meter readers received an electric shock.

In both incidents, the meter readers tested the outside of the meter box with a proximity voltage tester to check it was not live. However, upon touching the electricity meter’s scroll button, they received an electric shock.

ADVERTISEMENT

The electricity distributor found power monitoring devices attached to the switchboard had leaked battery acid onto the electricity meter creating an unsafe situation.

In this case, WorkSafe Queensland recommends that electricians check for the presence of these devices when first opening the switchboard, noting they may be installed in hard-to-see locations.

Maintain battery-powered devices such as energy monitoring systems, timeclocks or communication equipment. If these devices are not maintained they can leak an alkaline substance onto equipment located below, creating a potential electric shock hazard and damaging equipment.

If batteries have leaked, make note of the extent of the leakage and ensure suitable controls are in place to eliminate the shock hazard and chemical exposure. This may include advising the owner to have the device and associated cabling removed.

WorkSafe Queensland adds that to avoid the risk to equipment and people, unused battery-powered devices should have their batteries removed and be located so that battery leakage does not endanger other electrical equipment or be removed (including any associated cabling).

Previous Article

Turck Australia releases M12 connectors and receptacles ...

Next Article

element14 now stocking new-to-market smart gate drivers ...

  • ADVERTISEMENT

  • ADVERTISEMENT

Issue 1, 2025
Subscribe Now

Advertisement

Sign up to our newsletter

Advertisement

  • Home
  • About Electrical Connection
  • Download Media Kit
  • Contribute
  • Contact Us